Comprehensive Guide for Standby Diesel Generator Set Selection

Blog, Generator Buying Guide 11/07/2025

Emergency and Standby Diesel Generator Set Selection & Sizing

Emergency generator sets are primarily used in critical locations to rapidly restore and extend power supply during emergencies, accidental outages, or instantaneous power failures. Loads powered by these systems are categorized as Grade I (primary) loads. For equipment, instrumentation, and computer systems with stringent requirements on power interruption time, it is essential to supplement the generator set with a battery pack or Uninterruptible Power Supply (UPS).

Emergency generator sets operate under two key characteristics:

  1. Emergency Use: They are designed for short continuous operation, typically running for only a few hours (less than 12 hours).
  2. Standby Function: These units remain in a standby state, activated only when all primary power sources fail. They supply power to critical emergency loads and automatically shut down after primary power is restored.
Chinese Diesel Generator

1. Emergency Diesel Generator Set Selection Criteria

1.1. Determining Emergency Generator Capacity

The rated capacity of an emergency diesel generator set is its 12-hour rated output, adjusted for atmospheric conditions. This capacity must meet the total calculated emergency electrical load and be verified against the requirement of starting the single largest motor within the Grade I load. Emergency generators are typically three-phase, brushless AC synchronous generators with a standard rated output voltage of 400V.

1.2. Determining the Number of Emergency Generator Sets

Generally, one emergency diesel generator set is sufficient for the emergency load capacity. However, two or more units can be configured for parallel operation. With advancements in paralleling technology, there are instances in data centers where 20 or more diesel generators operate in parallel (see Chapter 7 for details). When selecting multiple units, prioritize identical models, similar capacities, and comparable voltage regulation and speed governing characteristics. Using consistent fuel types simplifies operation, maintenance, and spare parts management. For a two-unit emergency backup system, the automation system should enable mutual redundancy. Upon a confirmed utility power failure, an automatic start command is issued. If the first unit fails to start after three consecutive attempts, an alarm activates, and the second unit automatically starts.

1.3. Choosing the Emergency Generator Set Model

Select emergency generators known for high thermal efficiency, turbocharging, low fuel consumption, high reliability, and appropriate capacity. Turbocharged diesel engines offer higher power density and a smaller footprint. Engines should be equipped with electronic speed governors for superior performance. Generators should be synchronous types capable of handling loads as low as 40% of their rated capacity without adverse effects.

1.4. Emergency Generator Set Control Systems

Control systems for emergency diesel generators must feature rapid and reliable automatic start and load acceptance capabilities. Following a primary power failure, the emergency set must start automatically and restore power quickly. The allowable power interruption time for Grade I loads ranges from tens of seconds; specific requirements depend on the load profile. In practice, after a main power failure, a 3-5 minute confirmation delay is standard to check for transient faults or backup power restoration. Subsequently, the start command is issued. The process from command to startup, speed stabilization, and full load acceptance takes a finite time. Large and medium-sized diesel engines often require pre-lubrication and pre-heating to ensure oil and coolant temperatures meet technical specifications. Therefore, emergency generators must be maintained in a pre-lubricated and pre-warmed state for swift starting and minimized outage duration.

After the emergency generator set is running, to minimize mechanical and current shock from sudden load application, it is advisable to sequentially add emergency loads with time delays, provided power supply requirements are met. For automated diesel generator sets, the initial permissible load after a successful start is typically: not less than 50% of the rated load for sets under 250 kVA; for sets above 250 kVA, follow the manufacturer’s technical specifications. If transient voltage dip and recovery are not critical, the sudden load application or removal should generally not exceed 70% of the unit’s rated capacity.

2. Prime & Continuous Diesel Generator Set Selection

Certain diesel generator sets are intended for extended or continuous operation as the primary power source for electrical loads; these are termed Prime Power generator sets. They can serve as both continuous and standby power sources. In remote areas like towns, islands, forests, mines, and oil fields, or for specific industrial enterprises supplying local production and domestic electricity, diesel generators are installed for continuous operation.

Critical facilities such as national defense projects, communication hubs, broadcasting stations, and microwave relay stations must have standby diesel generators. While normally powered by the utility grid, these generators must start promptly and run continuously for extended periods during natural disasters (e.g., earthquakes, typhoons) or human-induced events to ensure an uninterrupted power supply for vital loads. This type of standby generator also falls under the Prime Power category. Given their long operational hours and variable load profiles, the selection of capacity, number of units, type, and control mode for Prime Power sets differs from Emergency sets.

2.1. Determining Prime Power Generator Capacity

Select the capacity based on the Long-Term Operating Power output, which should satisfy the maximum calculated process load. The capacity of the standby unit should be determined based on load criticality. The continuous power output for a diesel generator set is typically 0.9 times its prime power rating. The generator’s rated voltage is determined similarly to emergency sets, usually 400V. For projects with high power demand and long transmission distances, high-voltage generator sets may be suitable.

2.2. Determining the Number of Prime Power Generator Sets

Prime power installations typically require two or more units to ensure power supply continuity and adapt to load profile variations. Multiple units allow for adjusting the number of online generators based on load demand, keeping the diesel engines operating within the economical load range (typically 75%-90% of rated power), reducing fuel consumption and lowering generation costs. To guarantee continuity, a standby generator set should be incorporated within the prime power system, ensuring an uninterrupted supply to critical loads during maintenance or failure of a running unit.

2.3. Prime Power Generator Set Control

Prime power diesel generator sets should generally be designed for parallel operation to simplify the main electrical distribution system. This allows for load transfer and unit switching without interrupting the power supply during scheduled rotation. Generator sets must be equipped with comprehensive measurement and control systems. The engine speed governing and generator excitation systems must be suitable for parallel operation. Standby generators for critical loads should be automated units capable of automatic and rapid starting upon external power failure. Since diesel engines are noisy during operation, automated sets facilitate remote control and monitoring, allowing operators to manage the generators from a control room without entering the generator hall.

3. Specific Generator Set Application Types & Configurations

To adapt to diverse environmental conditions and special requirements, diesel generator sets are available in various types with numerous optional accessories. Adding these accessories enhances functionality, enables operation in harsh environments, meets the demands of sensitive loads, and fulfills varying levels of automation needs. Below are selections for typical accessories and different generator set types.

3.1. Selection of Generator Set Accessories

  • Jacket Water Heater: For liquid-cooled sets in regions below 0°C, a jacket water heater raises coolant temperature, improves fluidity, and warms the engine block via heat transfer, solving cold-start difficulties.
  • Anti-Condensation Heaters: For generators or control panels stored in high-humidity or cold environments, these heaters reduce internal moisture and minimize static electricity effects in winter.
  • Battery Charger: A mains-powered battery charger maintains the starter battery at full capacity through boost or float charging, crucial for standby and automated sets requiring immediate readiness.
  • Electronic Speed Governing & Electronic Diesel Control (EDC): Sets with electronic governors (including EDC engines) offer significantly better frequency stability and smaller speed droop compared to mechanical systems. This results in smaller frequency and voltage fluctuations, making them ideal for sensitive loads like computers and UPS systems. Electronic governors are also mandatory for parallel operation of multiple generator sets.
  • Other Accessories: Options include high/low fuel level switches, ground fault protection, and automatic fuel refilling systems. These must be pre-ordered and installed by qualified personnel.

3.2. Selection of IP (Ingress Protection) Rating

In diesel generator sets, preventing the entry of foreign objects and moisture into the AC generator is critical to avoid phase-to-phase short circuits and burnout. Since complete sealing is impossible due to cooling needs, selecting the appropriate IP rating is essential.

Hosem Machinery Diesel generator sets adhere to the IP rating standard (IEC 60529). The first numeral indicates protection against solid objects, and the second against moisture. Standard ratings are typically IP22 or IP23, with upgrades available to IP44 or IP55. Refer to Tables 1-5 and 1-6 for detailed definitions. Choose the IP rating based on the operating environment. IP23 is a marine standard. For very dusty environments (e.g., sawmills), consider IP44 or IP55. IP44 typically adds air intake and exhaust filters to an IP23 base, while IP55 involves a jacket water heat exchanger for the generator.

3.3. Selection of Heat Exchanger

The standard cooling system for diesel generator sets is an integral radiator/fan assembly. Its advantage is operational independence from external water sources, ideal for arid regions. However, this increases the overall footprint, and the cooling fan significantly contributes to noise.

A heat exchanger system overcomes these drawbacks. Replacing the radiator with a heat exchanger drastically reduces noise and physical size, allowing installation in compact spaces or residential areas. However, this requires external space for a cooling tower or circulation pond, adding to infrastructure costs. This system is suitable for power supply in densely populated areas like residential zones, shops, and hotels.

3.4. Application of PMG (Permanent Magnet Generator) Excitation Systems

Excitation System

In PMG series brushless AC synchronous generators, the Automatic Voltage Regulator (AVR) is powered by a separate permanent magnet pilot exciter, independent of the generator’s main output. During load or speed transients, this system is unaffected by the generator’s mechanical transition process, allowing rapid output voltage correction. Consequently, PMG generators have a far superior dynamic voltage regulation performance and better stability compared to other excitation systems. Conventional shunt excited generator AVRs are more susceptible to load current waveform distortions, especially from non-linear loads. PMGs also offer low electromagnetic interference, high efficiency, low temperature rise, and robustness in harsh environments. They are recommended for:

  • Applications demanding high power quality: minimal voltage fluctuation, clean output waveform, and low transient response (e.g., precision electronic instruments).
  • Locations with strict limits on electromagnetic interference (e.g., communication equipment, radar, precision control systems).
  • Harsh operating conditions: high ambient temperatures, high engine speeds, or large torque variations.
  • Scenarios with stringent energy efficiency requirements: limited fuel supply or constrained engine power.

3.5. Selection of Parallel Operation Systems

Considering factors like load magnitude and operational strategy, parallel operation of multiple generator sets is sometimes necessary. This increases backup power redundancy, handles very large loads, or addresses situations where a large motor starting current necessitates a large set, but normal running load is low and inefficient. A parallel start followed by single-unit operation can be used.

For synchronizing a generator to a live bus, conditions of equal voltage, equal frequency, same phase sequence, and phase angle must be met.

Hosem Machinery offers advanced, proven paralleling systems centered on the TC3.0 Intelligent Controller. This microprocessor-based controller provides real-time monitoring and control. For load sharing, it proportionally distributes the load based on preset parameters and automatically synchronizes or disconnects units based on total load, optimizing economy and ensuring healthy engine operation.

3.6. Selection of Automation Level


Hosem Machinery generator sets are broadly categorized into Manual, Automatic, and Remote Control types based on automation level. Users can select the control system per their needs:

  • TCL0 Control Panel: For manual/local operation and automatic start.
  • TC2.0 Control Panel: For remote control with “Three Remote” functions (Telemetry, Tele-signaling, Tele-control).
  • TC3.0 Intelligent Controller: For parallel operation systems.
    When any intelligent controller is integrated with an Automatic Transfer Switch (ATS), automatic switching between utility mains and generator power is achieved.

4. Generator Set Capacity Estimation

Accurately estimating generator set capacity is crucial and complex. Undersizing leads to failure to carry the load or stalling during large motor starts. Oversizing increases capital and maintenance costs, wasting resources. Furthermore, prolonged operation at very light loads (underloading) causes carbon buildup on piston rings and injectors, accelerates cylinder wear, and can damage the engine. Therefore, capacity estimation must consider multiple factors: operating environment, load types, and future expansion margins.

4.1. Influence of Operating Environment


Ambient conditions directly impact a generator set’s output power. Key factors are ambient temperature, altitude, and relative humidity. High temperatures or high altitudes reduce air density, diminishing combustion air supply and requiring derating of the engine’s output. The selected set’s rated power must be higher than the absolute load power requirement. Diesel generator set ratings are typically defined at standard conditions (e.g., 27°C, 152.4m altitude, 60% relative humidity). Power correction calculations are required for non-standard conditions (detailed in this chapter).

Notably, Electronic Controlled Diesel Engines (EDC), with precise electronic fuel injection management, experience less power degradation in non-standard environments compared to mechanically governed engines.

4.2. Influence of Load Types

Different load types impose varying demands on generator set capacity. Loads are generally categorized as Resistive, Inductive (linear), and Non-Linear (rectifier-based).

  • Resistive Loads: Incandescent lamps, electric heaters, ovens.
  • Inductive/Rectifier Loads: AC motors, machine tools, pumps.
  • Non-Linear Loads: UPS systems, computers, PLCs, program-controlled switches.
    For pure resistive loads, generator capacity need only slightly exceed the load power. For inductive and non-linear loads, careful recalculation is essential.

4.2.1. Impact of Inductive Loads on Capacity

Voltage regulation accuracy

Inductive loads like 3-phase squirrel-cage induction motors have high intrush starting currents (5-7 times full load current) and a low starting power factor. Direct-on-line starting requires a generator large enough to handle the intrush, leading to inefficient, oversized units for normal running.

Example: Supplying a 55kW motor (380V, PF=0.89, Efficiency=92%, 5x starting current).
Full Load Current (FLC) = 55,000 / (√3 * 380 * 0.89 * 0.92) ≈ 102A.
A 70kVA set (126A max) might suffice for running.
Starting Current = 5 * 102A = 510A. To start, a ~300kVA set (532A max) is needed – highly inefficient for normal operation.

To reduce starting impact, use reduced-voltage starting methods:

  1. Star-Delta (Wye-Delta) Start
  2. Auto-transformer Start
  3. Primary Resistance Reactor Start
  4. Soft Starter Start
  5. Variable Frequency Drive (VFD) Start

Star-Delta starting current is about 1/3 of DOL. Other methods reduce current proportional to the voltage reduction.

4.2.2. Impact of Non-Linear Loads on Capacity

Non-linear loads (e.g., computers) cause intrush currents, harmonic feedback, and current step changes, often with strict voltage dip requirements. Generator output voltage distortion is inherently higher, and smaller sets have higher internal impedance, exacerbating the issue. While Hosem sets have excellent electrical performance, selecting a larger capacity is often prudent for safety and performance. Larger units produce smaller voltage dips with the same load. When supplying UPS systems without input filters, SHUNT excited generators often need 2-2.5 times the UPS kVA rating. Using UPS with high-efficiency input filters or PMG generator sets allows for much closer capacity matching.

Always analyze specific load characteristics for accurate sizing. See Table 1-7 for reference data on starting and running currents for different loads.

Table 1-7: Starting & Running Currents for Different Load Types

Load TypeStarting Current (x FLC)Running Current (x FLC)
Incandescent Lamps / Heaters (Resistive)1.01.0
Fluorescent Lamps / HID (Discharge)2.1 – 2.81.2 – 1.6
Power Supplies / VFDs (AC-DC)2.0 – 3.01.3 – 1.6
3-Phase Induction Motors (Inductive)5.0 – 6.01.3 – 2.0

4.3. Other Considerations

After calculating capacity based on existing loads, include factors like potential overloads and future expansion plans. It is advisable to incorporate a reasonable capacity margin.

Where economically feasible, using two or more generator sets is recommended – dedicating one set to sensitive loads (computers, electronics) and another to non-sensitive loads (resistive, motors). This prevents voltage waveform distortion caused by motor loads from affecting sensitive equipment.

5. Special Application & Packaged Generator Sets

The development and application of special-purpose and packaged generator sets have expanded their usage, offering users wider choices. Examples include:

  • Sound-Attenuated Canopy Sets: For noise-sensitive locations.
  • Mobile/Trailer-Mounted Sets: For short-distance emergency power or construction site use within urban areas.
  • Vehicle-Mounted Power Stations: Self-powered, mobile units for long-distance emergency power supply.
  • Containerized Generator Sets: House large units while providing weatherproofing and sound attenuation.